Dome Slit

Drawing:RCT001.10
EOS Drawing SCH-4031-1
Manual: MM 18-14
Drop Leaf Motor: Leeson Model 111950 
Slit Motor: 3 HP Leeson Model 1740RPM 130323
Motor Encoder: none
Overall Encoder: none
Shutter Limits: open, closed, midway 
Dropleaf: open,closed
Control:Crydom relays D2450
Controller: Allen Bradley PICO 
Phase enable relay: Crydom D53TP50D
Homing: none needed
Interface: Relays 
Slip Rings: twelve

There is a power inverter that seems to be obsolete.

Vendor: Anacon Systems
Model: ED3-42100
I do not have notes on what the values are but here are some guesses from reading the manual. The closing speed should be about 40 Hz, I am not sure if this is set by P01 or P20.
P value purpose reason
01 50 Hz max speedThis or P20 sets closing speed of 50 Hz
02 0 Hzmin speed default
03 5 secacc time default
04 5 sec slow timedefault
05 0? stop modedefault -
06 0 V/F modedefault
07 0 rapid deaccdefault
08 19.5 rated current default ?
09 60 rated frequency this is america
10 0 rated speed deal in hz not rpm
11 2 % boost a bit less than default
12 0 keypad selectdefault-external input
13 log event log default
14 101 codedefault - i pray
Here are the advanced codes.
P value purpose reason
15 230 rated voltagedefault - 220V
16 0-10V analog inputdefault - not used!
17 4kHz switching frequency slower than default -
18 0 relay outputdefault - we need it
19 4 moded1-enable,d2-dir,d3-gnd important
20 50 Hz Preset speed 1closing speed
21 0 Preset speed 2default - not used
22 0 Preset speed 3default - not used
23 0 Preset speed 4default - not used
24 100 % slip compensationdefault - not used
25 0 analog ouputdefault - not used
26 100 % V/F characterdefault - not used
27 0 skip freqdefault - not used
28 0 skip freqdefault - not used
29 0 V/Fdefault - not used
30 Auto-0 start modedefault - not used
31 0 % DC injectiondefault - not used
32 0 % DC brakingdefault - maybe used
33 0 % DC braking enabledefault - ?
34 1 DC braking resistor enablebraking used?
35 84 % analog scalingdifferent from default- not used
36 0 Drive addressdefault
37 101 access codedefault - i pray
38 0 access lockdefault -
39 xxx hours runwhatever it says
40 xxx software checksumwhatever it says
Notes:
P-14 can be used to get keypad control
It is possible to restore factory defaults: see page 26 of manual.

The dome shutter is composed of two parts. The main part which goes up and over the top and the "dropleaf". The sequence is discussed in great detail in the MM:18-14 Midway is closer to closed and tells when dropleaf can be activated. There is a maintenance panel shown on SCH-4033-1.

Software

rslit

Photos

Picture of the slit motor

Slit control panel.